FLW34 Outdoor/Overheas Pole Mounted SF6 Load Break Switch

Product Overview
  • Material: Copper with Silver Glavizanition, Silicon or Porcelain Insulator
  • Rated Voltage: 12kV, 15kV, 24kV, 27kV, 36kV
  • Rated Current: 630A, 1250A
  • Standards: IEC 62271-102
  • Outdoor Pole Mounted

General

FLW34 pole mounted SF6 load break switch is used for breaking rated voltage 12/24/40.5kV,rated current 630A、50/60Hz power distribution system, closing load current and over load current of power system, it could separate automatically track sections of power distribution which faults occur. The switch is matched with electronic controller which is with the latest technology. The switch has manual, motor, remote operation modes. The electronic controller would be installed inside the stainless steel box, so it could be used in various climate conditions. Besides that, the wire/wireless modem installed inside control box could achieve remote monitoring and controlling. It’s easy and convenient for installation the switch on pole, and that could reduce the execution cost.

Technical Data

Technical specification Switch Disconnector Type FKW18
Rated Voltage(Ur) kV 12/24 33/36
Rated Current (Ir) A upto 2000
Power Frequency (Fr) Hz 50/60
Rated Power Freuqncy Withstand Voltage 1min.
&nbsp&nbsp&nbsp&nbsp- across isolating distance kV 60 80 130
&nbsp&nbsp&nbsp&nbsp- to earth and between phases kV 50 70 115
Rated Lightning Impulse (1.2/50μs impulse wave)
&nbsp&nbsp&nbsp&nbsp- across isolating distance kV 170 195 200 230 260
&nbsp&nbsp&nbsp&nbsp- to earth and between phases kV 150 170 200 225
Arcing Distance mm 225 380 380 437
Insulator Material Porcelain Polymer Porcelain Polymer Porcelain Cycloaliphatic
Creepage Distance mm 380 610 660 1055 1060 1370
Cantilever Strength kN 7.5 9.5 5.5 7 5.5 5.5
Minimum Distance Between Phases mm 350 380 450 500
Minimum Isolating Distance mm 220 320 380 380
Rated Short-time Current, 800A unit
&nbsp&nbsp&nbsp&nbsp-1 second kA 25 31.5
&nbsp&nbsp&nbsp&nbsp-3 second kA 20 25
Rated Peak Withstand Current kAp 62.5 78.75
Mechanical Endurance Ops 1000
Ambient Temperature Range -40…+40
Load Break Interrupter
&nbsp&nbsp&nbsp&nbsp- Rated Mainly Active Load Breaking Current (I1) A 630
&nbsp&nbsp&nbsp&nbsp- Rated Closed Loop Breaking Current (I2a) A 630
&nbsp&nbsp&nbsp&nbsp- Rated No Load Transformer Breaking Current(I3) A 10
&nbsp&nbsp&nbsp&nbsp- Rated Cable Charging Breaking Current (I4a) A 18
&nbsp&nbsp&nbsp&nbsp- Rated Line Charging Breaking Current(I4b) A 2
&nbsp&nbsp&nbsp&nbsp- Mechanical Endurance Ops 1000

Drawing

Packing Details

ModelDescriptionGross Weight/kgsNet Weight/kgsVolumn/m3Packing Size/m
FKW18-12     
FKW18-24     
FKW18-33     
FKW18-36     

Additional Resources

Products Catalogues

Installation Manual

Certifications

Contact Us

Recommend for you

记得增加系列产品链接

ru_RUРусский