FLW34 Outdoor/Overheas Pole Mounted SF6 Load Break Switch
- Material: Copper with Silver Glavizanition, Silicon or Porcelain Insulator
- Rated Voltage: 12kV, 15kV, 24kV, 27kV, 36kV
- Rated Current: 630A, 1250A
- Standards: IEC 62271-102
- Outdoor Pole Mounted
General
FLW34 pole mounted SF6 load break switch is used for breaking rated voltage 12/24/40.5kV,rated current 630A、50/60Hz power distribution system, closing load current and over load current of power system, it could separate automatically track sections of power distribution which faults occur. The switch is matched with electronic controller which is with the latest technology. The switch has manual, motor, remote operation modes. The electronic controller would be installed inside the stainless steel box, so it could be used in various climate conditions. Besides that, the wire/wireless modem installed inside control box could achieve remote monitoring and controlling. It’s easy and convenient for installation the switch on pole, and that could reduce the execution cost.
Technical Data
Technical specification Switch Disconnector Type FKW18 | ||||||||
Rated Voltage(Ur) | kV | 12/24 | 33/36 | |||||
Rated Current (Ir) | A | upto 2000 | ||||||
Power Frequency (Fr) | Hz | 50/60 | ||||||
Rated Power Freuqncy Withstand Voltage 1min. | ||||||||
    - across isolating distance | kV | 60 | 80 | 130 | ||||
    - to earth and between phases | kV | 50 | 70 | 115 | ||||
Rated Lightning Impulse (1.2/50μs impulse wave) | ||||||||
    - across isolating distance | kV | 170 | 195 | 200 | 230 | 260 | ||
    - to earth and between phases | kV | 150 | 170 | 200 | 225 | |||
Arcing Distance | mm | 225 | 380 | 380 | 437 | |||
Insulator Material | – | Porcelain | Polymer | Porcelain | Polymer | Porcelain | Cycloaliphatic | |
Creepage Distance | mm | 380 | 610 | 660 | 1055 | 1060 | 1370 | |
Cantilever Strength | kN | 7.5 | 9.5 | 5.5 | 7 | 5.5 | 5.5 | |
Minimum Distance Between Phases | mm | 350 | 380 | 450 | 500 | |||
Minimum Isolating Distance | mm | 220 | 320 | 380 | 380 | |||
Rated Short-time Current, 800A unit | ||||||||
    -1 second | kA | 25 | 31.5 | |||||
    -3 second | kA | 20 | 25 | |||||
Rated Peak Withstand Current | kAp | 62.5 | 78.75 | |||||
Mechanical Endurance | Ops | 1000 | ||||||
Ambient Temperature Range | ℃ | -40…+40 | ||||||
Load Break Interrupter | ||||||||
    - Rated Mainly Active Load Breaking Current (I1) | A | 630 | ||||||
    - Rated Closed Loop Breaking Current (I2a) | A | 630 | ||||||
    - Rated No Load Transformer Breaking Current(I3) | A | 10 | ||||||
    - Rated Cable Charging Breaking Current (I4a) | A | 18 | ||||||
    - Rated Line Charging Breaking Current(I4b) | A | 2 | ||||||
    - Mechanical Endurance | Ops | 1000 |