FLN48 Indoor SF6 Gas Insulated Load Break Switch

Product Overview
  • Material: Copper with Silver Glavizanition, Epoxy Resin Tank
  • Rated Voltage: 12kV, 15kV 
  • Rated Current: 630A 
  • Standards: IEC 62271-102
  • Use for Air Switchgear, Ring Main Units
  • Arc-extinguish: SF6 Gas
FLN48 Indoor SF6 Gas Insulated Load Break Switch
General
FL(R)N48 Indoor AC High Voltage SF6 Load Break Switch and LBS-Fuse Combination are used for the three-phase AC 50/60Hz RMU and terminal power station. The switches are suitable for protecting the 12kV power system’s on load situation. The switch can switch off the on load current, closed loop current, no load transformer capacity and cable charging current. The switch with fuse combination can cut off any current, when the current is in the range of the rated short-circuit breaking current. They are suitable for the RMU, combined transformer, etc..
Technical Data
Technical specification FLN48
Rated Voltage kV 12
Rated Current A 630
Rated Power Frequency Hz 50/60
Short Circuit Making Capacity kApeak 62.5
Peak Withstand Current kApeak 62.5
Short Time Current
– 1sec. kA 25
– 2Sec. kA 20
Max. Breaking Capacity in Co-operation with Fuses (test duty 4, IEC 62271-105) A 1530
Mainly Active Load Breaking Capacity A 630
Cable Charging Current A 630
Max. fuse current(XRNT Fuse) A 200
Power frequency withstand voltage 50Hz 1 min.
– To earth and between poles kV 42
-Across isolating distance kV 45
Impulse Withstand voltage 1.2/50μs
– To earth and between poles kV 75
-Across isolating distance kV 85
Mechanism Endurance cycles 1000

Drawings

Packing Details

ModelDescriptionGross Weight/kgsNet Weight/kgsVolumn/m3Packing Size/m
FLN48-1212kV SF6 LBS P=210mm48450.180.79×0.44×0.52
      
      
      

Additional Resources

Products Catalogues

Installation Manual

Certifications

Contact Us

Recommend for you

记得增加系列产品链接

ru_RUРусский
Прокрутить вверх