NPS Outdoor Air Load Break Switch

Product Overview
  • Material: Copper with Silver Glavizanition, Silicon or Porcelain Insulator
  • Rated Voltage: 12kV, 15kV, 24kV, 27kV, 36kV
  • Rated Current: 630A, 1250A
  • Standards: IEC 62271-102
  • Outdoor Pole Mounted

General

NPS series outdoor air break disconnector( air load break switch) is designed and tested for outdoor distribution and substation applications with voltage rating up to 36 KV and current rating up to 2000 Amps. The disconnector unit can be upgraded to include load break interrupters for general purpose switching performance. The NPS Series Switch/Disconnector can be operated either manually or remotely using a motorized unit.

Key Features

— Complies with AS60251-1 and IEC 60265-1

— Horizontal and Vertical break operation
— Rated voltage: 12, 24 and 36 kV
— Rated current: 800, 1200 and 2000 A
— Up to 225 kV BIL
— Porcelain, polymer or cycloaliphatic insulators

— Choice of operating mechanisms: Vertical handle, hook stick, motorized and auxiliary switch
— Flexible installation and mounting configurations (pole top, mid pole horizontal and mid pole vertical on single or H-POLE structure)
— Fully unitised and adjusted ready for installation or delivered in assembled phases for modular on-site assembly
— Designed and tested in accordance with IEC60265-1 Standard.
— Designed to be fitted with expulsion drop-out fuses or earthing switch
— Stainless steel and hot dip galvanized ferrous components resistant to corrosive environments
— Silver plated copper contacts
— Tin plated copper terminal palms

Technical Data

Technical specification Switch Disconnector Type FKW18
Rated Voltage(Ur) kV 12/24 33/36
Rated Current (Ir) A upto 2000
Power Frequency (Fr) Hz 50/60
Rated Power Freuqncy Withstand Voltage 1min.
&nbsp&nbsp&nbsp&nbsp- across isolating distance kV 60 80 130
&nbsp&nbsp&nbsp&nbsp- to earth and between phases kV 50 70 115
Rated Lightning Impulse (1.2/50μs impulse wave)
&nbsp&nbsp&nbsp&nbsp- across isolating distance kV 170 195 200 230 260
&nbsp&nbsp&nbsp&nbsp- to earth and between phases kV 150 170 200 225
Arcing Distance mm 225 380 380 437
Insulator Material Porcelain Polymer Porcelain Polymer Porcelain Cycloaliphatic
Creepage Distance mm 380 610 660 1055 1060 1370
Cantilever Strength kN 7.5 9.5 5.5 7 5.5 5.5
Minimum Distance Between Phases mm 350 380 450 500
Minimum Isolating Distance mm 220 320 380 380
Rated Short-time Current, 800A unit
&nbsp&nbsp&nbsp&nbsp-1 second kA 25 31.5
&nbsp&nbsp&nbsp&nbsp-3 second kA 20 25
Rated Peak Withstand Current kAp 62.5 78.75
Mechanical Endurance Ops 1000
Ambient Temperature Range -40…+40
Load Break Interrupter
&nbsp&nbsp&nbsp&nbsp- Rated Mainly Active Load Breaking Current (I1) A 630
&nbsp&nbsp&nbsp&nbsp- Rated Closed Loop Breaking Current (I2a) A 630
&nbsp&nbsp&nbsp&nbsp- Rated No Load Transformer Breaking Current(I3) A 10
&nbsp&nbsp&nbsp&nbsp- Rated Cable Charging Breaking Current (I4a) A 18
&nbsp&nbsp&nbsp&nbsp- Rated Line Charging Breaking Current(I4b) A 2
&nbsp&nbsp&nbsp&nbsp- Mechanical Endurance Ops 1000

Drawing

Packing Details

ModelDescriptionGross Weight/kgsNet Weight/kgsVolumn/m3Packing Size/m
FKW18-12     
FKW18-24     
FKW18-33     
FKW18-36     

Additional Resources

Products Catalogues

Installation Manual

Certifications

Contact Us