XTK-▢ Indoor SF6 Gas Insulated Two-Position Load Break Switch

Product Overview
  • Material: Copper with Silver Glavizanition
  • Rated Voltage: 12kV, 15kV, 24kV, 36kV, 40.5kV 
  • Rated Current: 630A, 1250A 
  • Standards: IEC 62271-102
  • Use for SF6 Gas Insulated Switchgear (GIS)
  • Arc-extinguish: SF6 Gas

XTK-◻ Indoor SF6 Gas Insulated Two-Position Load Break Switch

General

The 2-position load break switch for gas insulated switchgear includes: a movable portion of disconnector and main aix.

The Rated Voltage can use for 12kV, 24kV, 36kV. Rated Current can be 630A and 1250A. 

It is used for the SF6 Gas Insulated Switchgear. We design and teste as per IEC 62271-200, IEEE C37.20.9 and IEEE C37.20.7. Certificated in famous lab.

Technical Data

Technical specification XTK-□
Rated VoltagekV122436(40.5)
Rated CurrentA630630630
Rated Power FrequencyHz50/6050/6050/60
Short Circuit Making CapacitykApeak62.55050
Peak Withstand CurrentkApeak62.55050
Short Time Current
– 1sec.kA252525
– 2Sec.kA202020
Max. Breaking Capacity in Co-operation with Fuses
(test duty 4, IEC 62271-105)
A1530920630
Mainly Active Load Breaking Capacity
A
630
Cable Charging CurrentA630
Max. fuse current(XRNT Fuse)A200200100
Power frequency withstand voltage 50Hz 1 min.
– To earth and between poles
kV425595
-Across isolating distancekV4570120
Impulse Withstand voltage 1.2/50μs
– To earth and between poleskV75125190
-Across isolating distance
kV85145220
Mechanism Endurancecycles1000

Drawings

XTK-36 36kv Two Position SF6 Gas Load Break Switch

Packing Details

ModelDescriptionGross Weight/kgsNet Weight/kgsVolumn/m3Packing Size/m
FLN36-1212kV SF6 LBS P=210mm48450.180.79×0.44×0.52
      
      
      