XTV-▢ Indoor SF6 Gas Insulated Vacuum Circuit Breaker

Product Overview
  • Material: Copper with Silver Glavizanition
  • Rated Voltage: 12kV, 15kV, 24kV, 36kV, 40.5kV 
  • Rated Current: 630A, 1250A 
  • Standards: IEC 62271-102
  • Use for SF6 Gas Insulated Switchgear (GIS)
  • Arc-extinguish: SF6 Gas

XTV-◻ Indoor SF6 Gas Insulated Vacuum Circuit Breaker

General

The Vacuum Circuit Breaker for gas insulated switchgear includes: a vacuum interrupter, a disconnector. The disconnector can install for upper or lower side.

The Rated Voltage can use for 12kV, 24kV, 36kV. Rated Current can be 630A and 1250A. 

It is used for the SF6 Gas Insulated Switchgear. We design and teste as per IEC 62271-200, IEEE C37.20.9 and IEEE C37.20.7. Certificated in famous lab.

Technical Data

Technical specification XTV-□
Rated Voltage kV 12 24 36(40.5)
Rated Current A 630 630 630
Rated Power Frequency Hz 50/60 50/60 50/60
Short Circuit Making Capacity kApeak 62.5 50 50
Peak Withstand Current kApeak 62.5 50 50
Short Time Current
– 1sec. kA 25 25 25
– 2Sec. kA 20 20 20
Max. Breaking Capacity in Co-operation with Fuses
(test duty 4, IEC 62271-105)
A 1530 920 630
Mainly Active Load Breaking Capacity
A
630
Cable Charging Current A 630
Max. fuse current(XRNT Fuse) A 200 200 100
Power frequency withstand voltage 50Hz 1 min.
– To earth and between poles
kV 42 55 95
-Across isolating distance kV 45 70 120
Impulse Withstand voltage 1.2/50μs
– To earth and between poles kV 75 125 190
-Across isolating distance
kV 85 145 220
Mechanism Endurance cycles 1000

Drawings

12kV SF6 Lower Disconnector-VCB with Permanent Magnet Mechanism
12kV Lower Disconnector-VCB
12kV Upper Disconnector-VCB
36kV Upper Disconnector-VCB

Packing Details

ModelDescriptionGross Weight/kgsNet Weight/kgsVolumn/m3Packing Size/m
FLN36-1212kV SF6 LBS P=210mm48450.180.79×0.44×0.52
      
      
      